Power Line Communication (PLC)

What is PLC? 

Power line communication (PLC) is a communication method that uses the local power grid (230V) to provide an internet connection to other Power line devices (such as Zaptec Pro charging stations). The PLC module converts a standard Ethernet connection (network cable) into a signal sent over the local power grid (power line), removing the need for separate network cables to each charger.

  • Watch: PLC theory overview.
    The video uses a standard domestic PLC adapter. For best result, use the Zaptec-supplied DIN-rail PLC module.

PLC.png

 


 

Requirements and best practices

To ensure reliability: 

  • Minimum one PLC module per circuit.
  • Each PLC module can support up to ~30 chargers.
  • Ensure the protective earth (PE) is in good condition.
  • Zaptec Pro is wired 3-phase, but the PLC module should always be wired 1-phase (L1-N-PE). Charging stations communicate on PLC over L1 and N.
  • Maintain the same phase order across the entire charging system.
  • If the cable run is long, you may need multiple PLC models on the same circuit to maintain signal strength.
  • Install the PLC module in an enclosure close to the charging stations, preferably in the middle of the installation for even signal distribution.
  • The cable length must never be more than 90 meters.
  • Remove or isolate noise sources from the network.
  • Do not connect the PLC three-phase or to L2, L3, as this increases cable length and reduces signal strength. 

Long distances can impact the signal. The recommended cable length may vary depending on grid type, number of chargers, and noise from the power grid. For example, IT systems require shorter cable runs than TN systems.

Zaptec_Pro_PLC_2.jpg
The illustration is not intended to be used as a wiring diagram. The PLC connection must be protected by a suitably rated circuit breaker. The circuit on the left side of the picture illustrates that you might need to have multiple PLC modules on one circuit, depending on the length of the cable.

 


 

How to install the PLC module 

Zaptec Pro is wired 3-phase, and the PLC is wired 1-phase. If the PLC modules are fully encrypted, configure the charging stations as described in the procedure supplied with the PLC module. In the table below, you can see installation diagrams for TN and IT/TT grids.

  1. Mount the PLC module on a DIN rail, close to the charging stations, preferably in the middle of the installation for even signal distribution.
  2. Connect to the main power cabling and a standard Ethernet cable.
  3. It is recommended to install a 10A fuse before the PLC module.
  4. The module is usually mounted after a 63A course, but the connection terminals are 1.5-2.5 mm². This also simplifies any troubleshooting and restart of the PLC module.

 

Wiring diagrams
 

        Connection TN system                                                      Connection IT system 

Screenshot_2023-01-10_at_22.52.58.png             Screenshot_2023-01-10_at_22.59.21.png

 


 

PLC module configuration

After the PLC is mounted, connect the charging stations to the PLC network using the Zaptec App. 

Modules purchased after Nov. 2019 come pre-encrypted with a QR code.
Modules purchased before Nov.2019 require manual key entry. 

Steps (repeat for each charging station)

  1. Open the Zaptec App and tap the three-dot icon (top-right).
  2. Select Configure products and connect via Bluetooth using the PIN code.
  3. Go to Network Settings > Configure PLC.
  4. Tap the Scan network name and use the camera to scan the QR code on the PLC module. (iPhone users can upload images from the gallery).
  5. Tap Save to connect.

6.5-inch_Screenshot_3.jpg6.5-inch_Screenshot_2.jpg6.5-inch_Screenshot_4.jpg

Use the existing network key to add another charging station:

  1. Open the Zaptec App and tap the three-dot icon (top-right).
  2. Select Configure products and connect via Bluetooth using the PIN code.
  3. Copy the network key from an online charging station.
  4. Follow the same procedure on the new charging station and paste the network key in the last paragraph under Set network key. Remember to tap Save.

 


 

PLC module indicator light 
 

Icon Color Status
mceclip1.png
Green PLC is connected to power 
mceclip1.png
No Light PLC is not connected to power
mceclip2.png
Red PLC communicates with charger(s)
mceclip2.png
Green PLC is not communicating with other units on the PLC network. This could be because the chargers are not encrypted with the same encryption key as PLC  
mceclip3.png
Green PLC is connected to network router 
mceclip3.png
No Light   PLC is not connected to open port on router. Even though it is communicating with router, it does not mean it has access to the internet.

 

 


 

Troubleshooting 

Factors that can affect the signal strength of the PLC network:
 

Cable length

  • Cable length has a direct effect on the signal strength of the charging stations.
  • Use minimum one PLC unit per cable run/course.
  • Place the PLC module close to the charging stations, especially if the supply from the switchboard is far away.
  • The charging stations communicate with the PLC only between L1 + N + PE.
  • Connection on the L2 and L3 terminals will lead to increased cable length the devices are trying to communicate.
     

Number of connected devices

  • A PLC module has a limit on the number of devices it can communicate with. The general recommendation is 30 charging stations per PLC module.  Exceeding this number will lead to unstable communication over the PLC.
  • Isolate PLC communication on each course by encrypting the PLC module and associated charging stations.
  • Minimum one PLC unit per cable run/course.

 

Grounding conditions

  • PLC communication uses the ground connection for positioning the frequency range. Poor grounding reduces range and stability.
  • If the ground connection is insufficient or affected by external factors like ground faults, this may result in the PLC not being able to maintain sufficient signal quality for stable communication.

 

Electrical noise and local power outages

  • Noise from external sources, like frequency converters, can disrupt PLC signals.
  • It can be difficult to map, but this can be limited by installing a filter before the PLC module.

 


 

Need more help?

 

 

 

Updated

Was this article helpful?

42 out of 60 found this helpful

Have more questions? Submit a request